Integrated totals - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - IEC 60870-5-101/104 Communication Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 16.02.2023

SSC600 and SSC600 SW IEC 60870-5-104 Communication Protocol Manual

Integrated totals counter values are derived from the IEC 61850 BCR (binary counter) class. Counter freezing means that the IEC 60870-5-104 stack latches the current BCR.actVal attribute to itself.

  • BCR.actVal
Table 1. Integrated totals

Type

ASDU

GI

15

M_IT_NA_1

Integrated totals

Event

37

M_IT_TB_1

Integrated totals with CP56Time2a