Functions, codes and symbols - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - IEC 60870-5-101/104 Communication Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 19.04.2023

SSC600 and SSC600 SW IEC 60870-5-104 Communication Protocol Manual

Table 1. Functions included in the relay
Function IEC 61850 IEC 60617 ANSI

Protection

Distance protection DSTPDIS Z< 21P,21N
Three-phase non- directional overcurrent protection, low stage PHLPTOC 3I> 51P-1
Three-phase non- directional overcurrent protection, high stage PHHPTOC 3I>> 51P-2
Three-phase non- directional overcurrent protection, instantaneous stage PHIPTOC 3I>>> 50P
Three-phase directional overcurrent protection, low stage DPHLPDOC 3I> -> 67P/51P-1
Three-phase directional overcurrent protection, high stage DPHHPDOC 3I>> -> 67P/51P-2
Non-directional earth- fault protection, low stage EFLPTOC Io> 51G/51N-1
Non-directional earth- fault protection, high stage EFHPTOC Io>> 51G/51N-2
Non-directional earth- fault protection, instantaneous stage EFIPTOC Io>>> 50G/50N
Directional earth-fault protection, low stage DEFLPDEF Io> -> 67G/N-1 51G/N-1
Directional earth-fault protection, high stage DEFHPDEF Io>> -> 67G/N-1 51G/N-2
Admittance-based earth-fault protection EFPADM Yo> -> 21NY
Multifrequency admittance-based earth-fault protection MFADPSDE Io> -> Y 67NYH
Wattmetric-based earth-fault protection WPWDE Po> -> 32N
Transient/intermittent earth-fault protection INTRPTEF Io> -> IEF 67NTEF/NIEF
Negative-sequence overcurrent protection NSPTOC I2>M 46M
Phase discontinuity protection PDNSPTOC I2/I1> 46PD
Residual overvoltage protection ROVPTOV Uo> 59G/59N
Three-phase undervoltage protection PHPTUV 3U< 27
Three phase overvoltage variation protection PHVPTOV 3Urms> 59.S1
Three-phase overvoltage protection PHPTOV 3U> 59
Positive-sequence undervoltage protection PSPTUV U1< 27PS
Negative-sequence overvoltage protection NSPTOV U2> 59NS
Frequency protection FRPFRQ f>/f<,df/dt 81
Three-phase thermal protection for feeders, cables and distribution transformers T1PTTR 3Ith>F 49F
Three-phase thermal overload protection, two time constants T2PTTR 3Ith>T/G/C 49T/G/C
Low-voltage ride- through protection LVRTPTUV UU 27RT
Directional reactive power undervoltage protection DQPTUV Q> -> ,3U< 32Q,27
Reverse power/ directional overpower protection DOPPDPR P>/Q> 32R/32O
Three-phase underimpedance protection UZPDIS ZZ 21G
Negative-sequence overcurrent protection for machines MNSPTOC I2>M 46M
Loss of load supervision LOFLPTUC 3I< 37
Motor load jam protection JAMPTOC Ist> 50TDJAM
Motor start-up supervision STTPMSU Is2t n< 49,66,48,50TDLR
Phase reversal protection PREVPTOC I2>> 46R
Thermal overload protection for motors MPTTR 3Ith>M 49M
Stabilized and instantaneous differential protection for two-winding transformers TR2PTDF 3dI>T 87T
Numerical stabilized low-impedance restricted earth-fault protection LREFPNDF dIoLo> 87NLI
Circuit breaker failure protection CCBRBRF 3I>/Io>BF 50BF
Three-phase inrush detector INRPHAR 3I2f> 68HB
Master trip TRPPTRC Master Trip 94/86
Arc protection ARCSARC ARC AFD
Load-shedding and restoration LSHDPFRQ UFLS/R 81LSH
Multipurpose protection MAPGAPC MAP MAP
Load blinder LBRDOB LB 21LB
Busbar differential protection BBPBDF 3Id/I 87BL
Busbar zone selection ZNRSRC ZNRSRC ZNRSRC
Control
Circuit-breaker control CBXCBR I <-> O CB 52
Disconnector control DCXSWI I <-> O DCC 29DS
Earthing switch control ESXSWI I <-> O ESC 29GS
Disconnector position indication DCSXSWI I <-> O DC 29DS
Earthing switch position indication ESSXSWI I <-> O ES 29GS
Emergency start-up ESMGAPC ESTART EST,62
Autoreclosing DARREC O -> I 79
Synchronism and energizing check SECRSYN SYNC 25
Tap changer control with voltage regulator OL5ATCC COLTC 90V
Condition monitoring and supervision
Circuit-breaker condition monitoring SSCBR CBCM 52CM
Runtime counter for machines and devices MDSOPT OPTS OPTM
Measurement
Three-phase current measurement CMMXU 3I IA, IB, IC
Sequence current measurement CSMSQI I1, I2, I0 I1, I2, I0
Residual current measurement RESCMMXU Io IG
Three-phase voltage measurement VMMXU 3U VA, VB, VC
Residual voltage measurement RESVMMXU Uo VG/VN
Sequence voltage measurement VSMSQI U1, U2, U0 V1, V2, V0
Three-phase power and energy measurement PEMMXU P, E P, E
Frequency measurement FMMXU f f
Tap changer position indication TPOSYLTC TPOSM 84T
Power quality
Voltage variation PHQVVR PQMU PQMV SWE,SAG,INT
Voltage unbalance VSQVUB PQUUB PQMV UB
Traditional LED indication
LED indication control LEDPTRC LEDPTRC LEDPTRC
Individual virtual LED control LED LED LED
Logging functions
Disturbance recorder (common functionality) RDRE DR DFR
Disturbance recorder, binary channels RBDR RBDR RBDR
Fault recorder FLTRFRC FAULTREC FR
Other functionality
Parameter setting groups PROTECTION PROTECTION PROTECTION
Time master supervision GNRLLTMS GNRLLTMS GNRLLTMS
IEC 61850-1 MMS MMSLPRT MMSLPRT MMSLPRT
IEC 61850-1 GOOSE GSELPRT GSELPRT GSELPRT
IEC 60870-5-104 protocol I5CLPRT I5CLPRT I5CLPRT
OR gate with two inputs OR OR OR
OR gate with six inputs OR6 OR6 OR6
OR gate with twenty inputs OR20 OR20 OR20
AND gate with two inputs AND AND AND
AND gate with six inputs AND6 AND6 AND6
AND gate with twenty inputs AND20 AND20 AND20
XOR gate with two inputs XOR XOR XOR
NOT gate NOT NOT NOT
Real maximum value selector MAX3 MAX3 MAX3
Real minimum value selector MIN3 MIN3 MIN3
Rising edge detector R_TRIG R_TRIG R_TRIG
Falling edge detector F_TRIG F_TRIG F_TRIG
Real switch selector SWITCHR SWITCHR SWITCHR
Integer 32-bit switch selector SWITCHI32 SWITCHI32 SWITCHI32
SR flip-flop, volatile SR SR SR
RS flip-flop, volatile RS RS RS
Minimum pulse timer second resolution, two channels TPSGAPC TPS 62TPS
Minimum pulse timer minutes resolution, two channels TPMGAPC TPM 62TPM
Pulse timer, eight channels PTGAPC PT 62PT
Time delay off, eight channels TOFGAPC TOF 62TOF
Time delay on, eight channels TONGAPC TON 62TON
SR flip-flop, eight channels, nonvolatile SRGAPC SR SR
Boolean value event creation MVGAPC MV MV
Integer value event creation MVI4GAPC MVI4 MVI4
Analog value event creation with scaling SCA4GAPC SCA4 SCA4
Generic control points SPCGAPC SPC SPCG
Local/Remote control CONTROL CONTROL CONTROL
Voltage switch VMSWI VSWI VSWI
Current sum CMSUM CSUM CSUM
Current switch CMSWI CMSWI CMSWI
SMV stream receiver (IEC 61850-9-2LE) SMVRCV SMVRCV SMVRCV
Redundant Ethernet channel supervison RCHLCCH RCHLCCH RCHLCCH
Ethernet channel supervision SCHLCCH SCHLCCH SCHLCCH
Received GOOSE binary information GOOSERCV_BIN GOOSERCV_BIN GOOSERCV_BIN
Received GOOSE double binary information GOOSERCV_DP GOOSERCV_DP GOOSERCV_DP
Received GOOSE measured value information GOOSERCV_MV GOOSERCV_MV GOOSERCV_MV
Received GOOSE 8-bit integer value information GOOSERCV_INT8 GOOSERCV_INT8 GOOSERCV_INT8
Received GOOSE 32- bit integer value information GOOSERCV_INT32 GOOSERCV_INT32 GOOSERCV_INT32
Received GOOSE interlocking information GOOSERCV_INTL GOOSERCV_INTL GOOSERCV_INTL
Received GOOSE measured value (phasor) information GOOSERCV_CMV GOOSERCV_CMV GOOSERCV_CMV
Received GOOSE enumerator value information GOOSERCV_ENUM GOOSERCV_ENUM GOOSERCV_ENUM
Bad signal quality QTY_BAD QTY_BAD QTY_BAD
Good signal quality QTY_GOOD QTY_GOOD QTY_GOOD
GOOSE communication quality QTY_GOOSE_COMM QTY_GOOSE_COMM QTY_GOOSE_COMM
GOOSE data health T_HEALTH T_HEALTH T_HEALTH
Fault direction evaluation T_DIR T_DIR T_DIR
Enumerator to boolean conversion T_TCMD T_TCMD T_TCMD
32-bit integer to binary command conversion T_TCMD_BIN T_TCMD_BIN T_TCMD_BIN
Binary command to 32- bit integer conversion T_BIN_TCMD T_BIN_TCMD T_BIN_TCMD
Switching device status decoder - CLOSE position T_POS_CL T_POS_CL T_POS_CL
Switching device status decoder - OPEN position T_POS_OP T_POS_OP T_POS_OP
Switching device status decoder - OK status T_POS_OK T_POS_OK T_POS_OK
Security application GSAL GSAL GSAL