Enabled by writing 1 to Prtl Customization. When effective Customization mode will indicate 1 or ‘Custom profile 1’. When enabled the following functionality changes are in effect:
- Measurements (analogue values) are sent cyclically using structured data (SQ=1) and with a configurable interval. In PCM600 Communication Management tool Configuration table view the measurements need to be configured with Action = ‘Cyclical Enabled’ and the Interval is used to configure the period. Period must be a multiple of the Cyclical Period application-level setting value.
- Integrated totals are sent cyclically using structured data (SQ=1), cause of transmission spontaneous (COT=3), interval = 4s and sequence number included in protocol flags.