The SV delay parameter, found via menu path , defines how long the receiver waits for the SMV frames before activating the SMVRECEIVE ALARM output. This setting also delays the local measurements of the receiver to keep them correctly time aligned. The SV delay values include sampling, processing and network delay.
SMVRECEIVE WARNING output is set TRUE if two consecutive frames are lost. ALARM output is set TRUE if three or more frames in a sequence is lost. A single loss of frame is corrected with a zero-order hold scheme, the affect on protection is considered negligible in this case and it does not activate the SMVRECEIVE WARNING or ALARM outputs.
|
SV Delay setting (%) |
Ethernet network margin (ms) |
Protection delay (ms) |
|---|---|---|
|
50 |
0,656 |
2,606 |
|
75 |
0,984 |
2,934 |
|
100 |
1,313 |
3,263 |
|
125 |
1,641 |
3,591 |
|
150 |
1,969 |
3,919 |
|
200 |
2,625 |
4,575 |
|
300 |
3,938 |
5,888 |
|
5000 |
65,625 |
67,575 |
|
SV Delay setting (%) |
Ethernet network margin (ms) |
Protection delay (ms) |
|---|---|---|
|
50 |
0,547 |
2,497 |
|
75 |
0,82 |
2,77 |
|
100 |
1,094 |
3,044 |
|
125 |
1,367 |
3,317 |
|
150 |
1,641 |
3,591 |
|
200 |
2,188 |
4,138 |
|
300 |
3,281 |
5,231 |
|
5000 |
54,688 |
56,638 |
Because SV delay impacts directly the protection speed, big values are meant for non-time critical applications, like alarming. Increasing SV delay might be necessary for high latency networks for example in case of mobile networks.
When using routable SV, there’s additional R-SV delay parameter that can be used to adjust the total network delay and therefore also the protection delay. The formula to calculate the total protection delay using R-SV delay is the following:
Where DelayEth is the Ethernet margin, DelayR-SV is the configured R-SV delay and SampleDistance is the SV sample distance in milliseconds. See table below for SV sample distances.
| SV Profile | SV sample distance (ms) |
|---|---|
| 9-2LE at 50 Hz | 0,250 |
| 9-2LE at 60 Hz | 0,208 |
| IEC 61869-9 at 50 Hz | 0,208 |
| IEC 61869-9 at 60 Hz | 0,208 |
For example, consider the R-SV delay setting of 0,5 ms, the SV delay setting of 100% using IEC 61869-9 at 50 Hz. The total protection delay would be the following: