SSC600 SW installations in general - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - Engineering Manual - SSC600 Smart substation control and protection - SSC600 - 1.5 - IEC - ANSI - 18.12.2024

SSC600 and SSC600 SW Engineering Manual

Before communication is enabled in SSC600 SW, it's important to note that some communication ports - like process bus - needs to be enabled separately from parameter settings. Port enabling parameters can be found in IED Configuration > Configuration > Communication > Ethernet

In addition the SSC600 SW ports needs to be attached to the physical Network Interfaces in the hardware. This can be achieved with the Network configuration -view in SSC600 SW WHMI.

If the HW used in SSC600 SW has a dedicated PRP card, it's important to note that on SSC600 side configuration should be for non-redundant communication. So PRP card does the PRP itself, without SSC600 SW not knowing about it.