Routable GOOSE - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - Engineering Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 17.04.2023

SSC600 and SSC600 SW Engineering Manual

R-GOOSE is GOOSE data sent over a WAN. R-GOOSE can be used for wide area protection and control applications. R-GOOSE follows the principles and configuration of GOOSE extending the transport medium to allow routing over IP networks. R-GOOSE messages are sent connectionless using IP multicast and UDP. R-GOOSE uses IGMPV3 to allow routers to determine the routing path through the network.