Importing a SSC600 protection device in a COM600S project - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - Engineering Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 13.05.2019

SSC600 and SSC600 SW Engineering Manual

  1. Create a PCM600 project including several IEDs.
    Figure 1. Creating a PCM600 project including several IEDs
  2. Export the SCD file from PCM600.
    In the Plant structure view, select the substation, right-click and select Export.
    Figure 2. Exporting SCD file from PCM600 and importing it to SAB600
  3. Import the SCD configuration into the SAB600 project. In the Project Explorer view, right-click the IEC61850 OPC Server object and select SCL Import.
    Figure 3. Importing the SCD configuration into the SAB600 project
  4. In the SCL Import view, click Select File to select the SCD file exported from PCM600.
    Figure 4. Creating a new IED into SAB600 project
  5. Check the default settings in the SCL Import view and change the settings if they are not suitable.
    The default settings in the SCL Import dialog should be correct in most cases.
  6. Click Import to import the SCD file.
  7. Check the IP address on the IEC 61850 subnetwork and change it if needed.
    When the SCD file is directly exported from PCM600, it uses the IP address of the PCM600 computer, not the COM600S.
The communication towards the IED is now ready. For information on how to finalize the single-line diagram and enable parameter setting through COM600S HMI, see COM600S documentation.