All available functions included in the IED are listed in the tables below. Available functions depend on the chosen product options.
| Function | IEC 61850 | IEC 60617 | ANSI |
Logical
device |
Logical nodes |
|---|---|---|---|---|---|
| Three-phase non-directional overcurrent protection, low stage | PHLPTOC | 3I> | 51P-1 | LD0 | PHLPTOC |
| Three-phase non-directional overcurrent protection, high stage | PHHPTOC | 3I>> | 51P-2 | LD0 | PHHPTOC |
| Three-phase non-directional overcurrent protection, instantaneous stage | PHIPTOC | 3I>>> | 50P | LD0 | PHIPTOC |
| Three-phase directional overcurrent protection, low stage | DPHLPDOC | 3I> -> | 67P/51P-1 | LD0 |
DPHLPTOC
DPHLRDIR |
| Three-phase directional overcurrent protection, high stage | DPHHPDOC | 3I>> -> | 67P/51P-2 | LD0 |
DPHHPTOC
DPHHRDIR |
| Non-directional earth-fault protection, low stage | EFLPTOC | Io> | 51G/51N-1 | LD0 | EFLPTOC |
| Non-directional earth-fault protection, high stage | EFHPTOC | Io>> | 51G/51N-2 | LD0 | EFHPTOC |
| Non-directional earth-fault protection, instantaneous stage | EFIPTOC | Io>>> | 50G/50N | LD0 | EFIPTOC |
| Directional earth-fault protection, low stage | DEFLPDEF | Io> -> | 67G/N-1 51G/N-1 | LD0 |
DEFLPTOC
DEFLRDIR |
| Directional earth-fault protection, high stage | DEFHPDEF | lo>> -> | 67G/N-1 51G/N-2 | LD0 |
DEFHPTOC
DEFHRDIR |
| Admittance-based earth-fault protection | EFPADM | Yo> -> | 21YN | LD0 | EFPADM |
| Wattmetric-based earth-fault protection | WPWDE | Po> -> | 32N | LD0 |
WRDIR
WPSDE WMMXU |
| Transient/intermittent earth-fault protection | INTRPTEF | lo> -> IEF | 67NTEF/NIEF | LD0 | INTRPTEF |
| Negative-sequence overcurrent protection | NSPTOC | I2> | 46M | LD0 | NSPTOC |
| Phase discontinuity protection | PDNSPTOC | I2/I1> | 46PD | LD0 | PDNSPTOC |
| Residual overvoltage protection | ROVPTOV | Uo> | 59G/59N | LD0 | ROVPTOV |
| Three-phase undervoltage protection | PHPTUV | 3U< | 27 | LD0 | PHPTUV |
| Three-phase overvoltage protection | PHPTOV | 3U> | 59 | LD0 | PHPTOV |
| Positive-sequence undervoltage protection | PSPTUV | U1< | 27PS | LD0 | PSPTUV |
| Negative-sequence overvoltage protection | NSPTOV | U2> | 59NS | LD0 | NSPTOV |
| Frequency protection | FRPFRQ | f>/f<,df/dt | 81 | LD0 |
FRPTRC
FRPTOF FRPTUF FRPFRC |
| Distance protection | DSTPDIS | Z< | 21P, 21N | LD0 |
GFCPDIS GFCRDIR DST1PDIS DST2PDIS DST3PDIS DST4PDIS DST5PDIS DSTRDIR GFC1RFRC GFC2RFRC GFC3RFRC |
| Three-phase thermal protection for feeders, cables and distribution transformers | T1PTTR | 3Ith>F | 49F | LD0 | T1PTTR |
| Three-phase thermal overload protection, two time constants | T2PTTR | 3Ith>T/G/C | 49T/G/C | LD0 | T2PTTR |
| Negative-sequence overcurrent protection for ma- chines | MNSPTOC | I2>M | 46M | LD0 | MNSPTOC |
| Loss of load supervision | LOFLPTUC | 3I< | 37 | LD0 | LOFLPTUC |
| Motor load jam protection | JAMPTOC | Ist> | 50TDJAM | LD0 | JAMPTOC |
| Motor start-up supervision | STTPMSU | Is2t n< | 49,66,48,50TDLR | LD0 |
STTPMSS
STTPMRI |
| Phase reversal protection | PREVPTOC | I2>> | 46R | LD0 | PREVPTOC |
| Thermal overload protection for motors | MPTTR | 3Ith>M | 49M | LD0 | MPTTR |
| Stabilized and instantaneous differential protection for two-winding transformers | TR2PTDF | 3dI>T | 87T | LD0 |
TR2PTRC TR2LPDIF TR2H2PHAR TR2H5PHAR TR2HPDIF |
| Numerically stabilized low-impedance restricted earth-fault protection | LREFPNDF | dIoLo> | 87NLI | LD0 |
LREFPDIF
LREFPHAR |
| Circuit breaker failure protection | CCBRBRF | 3I>/Io>BF | 50BF | LD0 | CCBRBRF |
| Three-phase inrush detector | INRPHAR | 3I2f> | 68HB | LD0 | INRPHAR |
| Switch onto fault | CBPSOF | SOTF | SOTF | LD0 | CBPSOF |
| Master trip | TRPPTRC | Master Trip | 94/86 | LD0 | TRPPTRC |
| Arc protection | ARCSARC | ARC | AFD | LD0 |
ARCSARC
ARC1PIOC ARC2PIOC ARCPTRC |
| Multipurpose protection | MAPGAPC | MAP | MAP | LD0 | MAPGAPC |
| Load-shedding and restoration | LSHDPFRQ | UFLS/R | 81LSH | LD0 |
LSHDPTRC
LSHDPTOF LSHDPTUF LSHDPFRC |
| Fault locator | SCEFRFLO | FLOC | FLOC | LD0 |
SCEFRFLO
SCEFZLIN SCEF2ZLIN SCEF3ZLIN FLORFRC |
| Reverse power/directional overpower protection | DOPPDPR | P>/Q> | 32R/32O | LD0 |
DPPDOP DOPMMXU |
| Three-phase underimpedance protection | UZPDIS | Z>G | 21G | LD0 |
UZPDIS UZMMXU |
| Multifrequency admittance-based earth-fault protection | MFADPSDE | Io> ->Y | 67NYH | LD0 |
MFADPSDE MFADRDIR |
| Busbar differential protection | BBPBDF | 3Id/I | 87BL | LD0 |
BBPTRC ZNAPDIF ZNBPDIF ZNCZPDIF SFAPDIF SFBPDIF BBCCSPVC |
| Busbar zone selection | ZNRSRC | ZNRSRC | ZNRSRC | LD0 | ZNRSRC |
| Load blinder | LBRDOB | LB | 21LB | LD0 |
LBRDOB
LBMMXU |
|
Three-phase overload protection for shunt capacitor banks |
COLPTOC |
3I> 3I< |
51,37,86C |
LD0 |
COL1PTOC COLPTUC COL2PTOC |
|
Current unbalance protection for shunt capacitor banks |
CUBPTOC |
dI>C |
60N |
LD0 |
CUB1PTOC CUB2PTOC |
|
Three-phase current unbalance protection for shunt capacitor banks |
HCUBPTOC |
3dI>C |
60P |
LD0 |
HCUB1PTOC HCUB2PTOC |
|
Shunt capacitor bank switching resonance protection,current based |
SRCPTOC |
TD> |
55ITHD |
LD0 |
SRC1PTOC SRC2PTOC |
|
Anomaly detector |
ANOGAPC |
ANOGAPC |
ANOGAPC |
LD0 |
ANOGAPC |
| Function | IEC 61850 | IEC 60617 | ANSI | Logical device | Logical nodes |
|---|---|---|---|---|---|
| Directional reactive power undervoltage protection | DQPTUV | Q> ->,3U< | 32Q,27 | LD0 |
DQPTUV DQPDOP DQMMXU |
| Low-voltage ride-through protection | LVRTPTUV | U<RT | 27RT | LD0 | LVRTPTUV |
| Function | IEC 61850 | IEC 60617 | ANSI | Logical device | Logical nodes |
|---|---|---|---|---|---|
| Current total demand distortion | CMHAI | PQM3I | PQM3I | CMHAI | CMHAI |
| Voltage total harmonic distortion | VMHAI | PQM3U | PQM3V | VMHAI | VMHAIVMHAI |
| Voltage variation | PHQVVR | PQMU | PQMV |
PHQVVR PH2QVVR PH3QVVR QVVRQRC QVV2RQRC QVV3RQRC |
PHQVVR PH2QVVR PH3QVVR QVVMSTA QVV2MSTA QVV3MSTA |
| Voltage unbalance | VSQVUB | PQUUB | PQVUB | - | - |
| Function | IEC 61850 | IEC 60617 | ANSI | Logical device | Logical nodes |
|---|---|---|---|---|---|
| Circuit-breaker control | CBXCBR | I <-> O CB | I <-> O CB | CTRL |
CBCSWI CBCILO CBXCBR |
| Disconnector control | DCXSWI | I <-> O DCC | I <-> O DCC | CTRL |
DCCSWI DCCILO DCXSWI |
| Earthing switch control | ESXSWI | I <-> O ESC | I <-> O ESC | CTRL |
ESCSWI ESCILO ESXSWI |
| Disconnector position indication | DCSXSWI | I <-> O DC | I <-> O DC | CTRL | DCSXSWI |
| Earthing switch indication | ESSXSWI | I <-> O ES | I <-> O ES | CTRL | ESSXSWI |
| Emergency start-up | ESMGAPC | ESTART | ESTART | LD0 | ESMGAPC |
| Autoreclosing | DARREC | O -> I | 79 | LD0 | DARREC |
| Tap changer position indication | TPOSYLTC | TPOSM | 84M | LD0 | TPOSYLTC |
| Tap changer control with voltage regulator | OLATCC | COLTC | 90V | LD0 | OLATCC |
| Synchronism and energizing check | SECRSYN | SYNC | 25 | LD0 | SECRSYN |
| Function | IEC 61850 | IEC 60617 | ANSI | Logical device | Logical nodes |
|---|---|---|---|---|---|
| Circuit-breaker condition monitoring | SSCBR | CBCM | CBCM | LD0 |
SSCBR1 SPH1SCBR SPH2SCBR SPH3SCBR SSOPM SSIMG |
| Runtime counter for machines and devices | MDSOPT | OPTS | OPTM | LD0 | MDSOPT |
| Fuse failure supervision | SEQSPVC | FUSEF | VCM, 60 | LD0 |
SEQSPVC |
| Function | IEC 61850 | IEC 60617 | ANSI | Logical device | Logical nodes |
|---|---|---|---|---|---|
| Disturbance recorder | RDRE | DR | DFR | LD0 |
DR_LLN0 DR_LPHD RDRE RBDR |
| Fault record | FLTRFRC | FAULTREC | FAULTREC | LD0 | FLTRFRC |
| Three-phase current measurement | CMMXU | 3I | 3I | LD0 |
CMMXU CAVMMXU CMAMMXU CMIMMXU |
| Sequence current measurement | CSMSQI | I1, I2, I0 | I1, I2, I0 | LD0 | CSMSQI |
| Residual current measurement | RESCMMXU | Io | In | LD0 |
RESCMMXU RCAVMMXU RCMAMMXU RCMIMMXU |
| Three-phase voltage measurement | VMMXU | 3U | 3V | LD0 |
VMMXU VAVMMXU |
| Residual voltage measurement | RESVMMXU | Uo | Vn | LD0 |
RESVMMXU RVAVMMXU RVMAMMXU RVMIMMXU |
| Sequence voltage measurement | VSMSQI | U1, U2, U0 | V1, V2, V0 | LD0 | VSMSQI |
| Three-phase power and energy measurement | PEMMXU | P, E | P, E | LD0 |
PEMMXU PEMMTR PEAVMMXU PEMAMMXU PEMIMMXU |
| Frequency measurement | FMMXU | f | f | LD0 | FMMXU |
| IEC 61850-9-2 LE sampled value receiving | SVRECEIVE_LE | SVRECEIVE_LE | SVRECEIVE_LE |
SMVRECEIVEMU01 – SMVRECEIVEMU30 |
I10ATCTR37 I10BTCTR38 I10CTCTR39 I10NTCTR40 U10ATVTR37 U10BTVTR38 U10BTVTR39 U10NTVTR40 |
| IEC 61869-9 sampled value receiving | SVRECEIVE_61869 | SVRECEIVE_61869 | SVRECEIVE_61869 |
SV61869RECEIVEMU01 – SV61869RECEIVEMU30 |
I01ATCTR1– I10ATCTR37 I01BTCTR2– I10BTCTR38 I01CTCTR3– I10CTCTR39 I01NTCTR4– I10NTCTR40 U01ATVTR1- U10ATVTR37 U01BTVTR2- U10BTVTR38 U01CTVTR3- U10CTVTR39 U01NTVTR4- U10NTVTR40 |
| Function | IEC 61850 | IEC 60617 | ANSI |
Logical
device |
Logical nodes |
|---|---|---|---|---|---|
| Minimum pulse timer | TPGAPC | TP | TP | TPGAPC | |
| Minimum pulse timer (second resolution) | TPSGAPC | TPS | TPS | TPSGAPC | |
| Minimum pulse timer minute resolution) | TPMGAPC | TPM | TPM | TPMGAPC | |
| Pulse timer | PTGAPC | PT | PT | PTGAPC | |
| Time delay off | TOFGAPC | TOF | TOF | TOFGAPC | |
| Time delay on | TONGAPC | TON | TON | TONGAPC | |
| Set-reset | SRGAPC | SR | SR | SRGAPC | |
| Move | MVGAPC | MV | MV | MVGAPC | |
| Generic control point | SPCGAPC | SPC | SPC | SPCGAPC | |
| Analog value scaling | SCA4GAPC | SCA4 | SCA4 | SCA4GAPC | |
| Integer value move | MVI4GAPC | MVI4 | MVI4 | MVI4GAPC | |
| Voltage switch | VMSWI | VSWI | VSWI | VMSWI | |
| Current switch | CMSWI | CMSWI | CMSWI | CMSWI | |
| Current sum | CMSUM | CSUM | CSUM |
SIL1TCTR SIL2TCTR SIL3TCTR SRESTCTR |