Defining GOOSE data set entries with the IEC 61850 Configuration tool - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - Engineering Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 16.02.2026

SSC600 and SSC600 SW Engineering Manual

  1. Select the Data Sets tab.
  2. Right-click a data set and select Details to add data attributes.
    Figure 1. Opening Details
  3. In the Data Set Entry window, select the data attribute or data object present in the data set.
    • Click Append selected to add the data to the end of the data set. To add a data object level entry, select it from the FC section. To add a data attribute level entry, select it from the DA section
    • Click Insert selected to add the data above the selected row in the data set entries list.
    • To remove a data from the data set, select the data in the data set entries pane and click Remove selected.

    A maximum of 80 data attributes can be added total to IED's GOOSE data sets. Recommendation is to divide attribute amount to 20 per GOOSE data set, for maximum performance in sender/receiver.

    Figure 2. Adding data set entries

    Note: If a data set has quality attributes, the attributes must be located after the status value of the same data object.
    Note: The data attribute entries are single data, such as stVal and q. Data set entries can be also defined on the data object level. Data object level GOOSE entries can only be received of the following CDC types: SPS, SPC, ACD, ACT, DPS, DPC, INC, INS, ENC and ENS. Some merging units (for example ABB 615 series ver. 5.0 or earlier) do not support the data object level GOOSE entries. This limitation must be considered when configuring the whole system consisting of different product versions.

    After defining the data entries for the data sets, configure the GOOSE control block properties.