Creating report control blocks with the IEC 61850 Configuration tool - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - Engineering Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 17.04.2023

SSC600 and SSC600 SW Engineering Manual

  1. Select the IED node in Plant Structure in Project Explorer.
  2. Click the Report Controls tab.
  3. Right-click the area containing the existing report control blocks and select New to add a new report control block.
    Figure 1. Adding a new report control block
  4. Browse to LLN0 under LD0 to define where to place the report control block.
  5. Give a unique name to the report control block.
  6. In the drop-down list, select the previously created data set to link with the GCB.
    Figure 2. Data set drop-down list
  7. Edit the properties and options of the created report control block.
    Figure 3. Report control block properties
    Note: Data set entries in a data set linked to the GCB can be modified from the GCB Control Block tab by selecting the Data Set Details in the shortcut menu.