Creating a complete HMI display page - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - Engineering Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 17.04.2023

SSC600 and SSC600 SW Engineering Manual

  1. Make a sketch of how to present the single-line diagram.
  2. Place the apparatus, transformer and other symbols that are needed for the single-line diagram into the raster boxes.
  3. Add Junction points where needed.
  4. Link the apparatus symbols with line elements.
  5. In the Object Properties view, adjust the text symbols while writing to north, east, south or west.
  6. Place measurements when needed.
  7. Edit the name, unit and the number of the measurements' decimals.
  8. Select each object that has a dynamic link and make the link to the corresponding process object.
  9. Check that the correct function block is selected.
    Function blocks of the same type can have different instance numbers.
    Figure 1. Graphical Display Editor: establishing a dynamic object link
  10. Ensure that all links are done.
  11. Save the complete picture.
  12. Write to the IED.
  13. Validate the single-line diagram on the IED.