Configuring Routable SMV sending with PCM600 - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - Engineering Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 18.12.2024

SSC600 and SSC600 SW Engineering Manual

R-SMV can be sent with dataset including measurements from a single received SMV from within a single logical device. The dataset configuration needs to be verified by user to reflect the received dataset. This is especially true for IEC 61869-9 datasets where the sent dataset current and voltage phases and measurement points need to be in line with the received dataset. This is important for the device receiving the R-SMV to be able to process the dataset correctly. The R-SMV dataset is sent as a copy of the received dataset values with no processing done to the values.

After all SVRECEIVE_LE connections have been added, the R-SMV sending can be configured.

  1. Open the IEC 61850 configuration tool in PCM.
  2. Select Process Bus Communication in the drop-down box on the toolbar.
  3. Make sure that the Data Sets tab is active.
  4. Create new data set from the SMVRECEIVE LD.
    1. Right click inside the IEC 61850 Configuration tool window.
    2. Select new in the context menu.
    3. Select the correct SMVRECEIVE LD item in the left-hand side tree.
    4. Select the ABB PhsMeas from the template drop-down.

    5. Press OK.
    6. Check the data set entries.

    7. Press OK.
  5. Switch to the Sampled Value Controls tab.
  6. Create a new Sampled Value Control.
    1. Right click inside the IEC 61850 Configuration tool window.
    2. Select new in the context menu.
    3. Select the SMVRECEIVE LD item that was used in the previous step.
    4. Select one of the ABB 9-2 LE templates from the drop down.
    5. Make sure that the Name attribute is unique for the SSC600.
    6. Make sure that the Routable checkbox is selected.
    7. Press OK.
  7. Configure R-SMV settings.
    1. VLAN, App ID and Sampled Value ID should be configured according to the same rules as for regular SMV streams.
    2. Set IGMPv3 Address to a valid unicast IP address.
    3. Set IP address to a unique UDP multicast address.
  8. In PCM600, select Write to IED.
    Note: Valid UDP multicast address range is 224.0.0.0 - 239.255.255.255. Valid unicast address range is 0.0.0.0 – 223.255.255.255.
Configuring the R-SMV reception is done the same way as for regular SMV.
Figure 1. Routable SMV settings