Configuring RCB clients with the IEC 61850 Configuration tool - Arc protection - Bay control and measurement - Motor protection - Transformer protection - 2 winding - Busbar differential protection (low impedance) - Feeder protection - Voltage regulation - Busbar protection (voltage and frequency) - Capacitor bank protection - Interconnection protection - Power management/Load shedding - Back-up protection - Engineering Manual - SSC600 Smart substation control and protection - 1.5 - IEC - ANSI - 17.04.2023

SSC600 and SSC600 SW Engineering Manual

Add and configure the IEDs before configuring the RCB client. The potential clients and their communication configuration should be known for a successful RCB client configuration.
Note: The RCB name is limited to 14 characters or 30 characters (without two-digit index number) depending on which IEC 61850 version is in use.
  1. In the Plant Structure, click the IED node which is RCB server.
  2. Click Report Controls tab.
    The rows of the Report Controls window show RCBs configured for the IED. The columns of the Report Controls window show the RCB clients configured in the PCM600.
  3. To add or remove clients for a report control block, click the check-box in the grid, corresponding to the client and RCB.
    Five clients at the maximum can be connected to a RCB.
    Figure 1. RCB clients
    1RCBs configured for the IED
    2RCB clients
    Note: The clients are added or removed automatically to the corresponding data sets in the Data Sets tab. Date sets are based on the configuration done in the Reports Controls tab and vice-versa.