All physical ports dedicated for station bus and process bus communication except local port can be opened and closed in device configuration. Local port is used for engineering and it can be used only for point-to-point configuration access with PCM600 or WHMI. Local port should not be connected to any Ethernet network.
Port ID | Type | Default state | Description |
---|---|---|---|
LAN1 | RJ-45 | Enabled | Local port |
LAN2 | RJ-45 | Disabled | Remote port (for engineering) |
LAN3 | RJ-45 or fiber optic | Disabled | Process bus A |
LAN4 | RJ-45 or fiber optic | Disabled | Process bus B |
LAN5 | RJ-45 | Enabled | Rear port |
LAN6 | RJ-45 | Disabled | not in use |
LAN7 | RJ-45 | Disabled | Service port |
LAN8 | RJ-45 | Disabled | not in use |
IEC 61850 protocol and LAN1 and LAN5 ports are by default activated as those are used for engineering of the protection device.