Warnings - Arc protection - Bay control and measurement - Merging unit - Operation Manual - SMU615 Substation Merging Unit - 1.0 - IEC - ANSI - 06.06.2023

SMU615 Operation Manual

An event about the warnings are stored with the text Warning additionally provided with the name of the warning, a numeric code and the date and time on the WHMI.

Note: If a warning appears, record the name and code so that it can be provided to ABB customer service.
Table 1. Warning indications and codes

Warning indication

Warning code

Additional information

Warning Watchdog reset

10

A watchdog reset has occurred.

Warning

Power down det.

11

The auxiliary supply voltage has dropped too low.

Warning IEC61850 error

20

Error when building the IEC 61850 data model.

Warning Dataset error

24

Error in the Data set(s).

Warning

Report cont. error

25

Error in the Report control block(s).

Warning

26

Error in the GOOSE control block(s).

GOOSE contr. error

Warning

SCL config error

27

Error in the SCL configuration file or the file is missing.

Warning Logic error

28

Too many connections in the configuration.

Warning

SMT logic error

29

Error in the SMT connections.

Warning

GOOSE input error

30

Error in the GOOSE connections.

ACT error

31

Error in the ACT connections.

Warning

GOOSE Rx. error

32

Error in the GOOSE message receiving.

Warning AFL error

33

Analog channel configuration error.

Warning

34

Error in the SMV configuration.

Warning

Comm. channel down

35

Redundant Ethernet (HSR/PRP) communication interrupted.

Warning

Unack card comp.

40

A new composition has not been acknowledged/accepted.