User authorization - Arc protection - Bay control and measurement - Merging unit - Operation Manual - SMU615 Substation Merging Unit - 1.0 - IEC - ANSI - 06.06.2023

SMU615 Operation Manual

The user categories have been predefined for the WHMI via front port RJ-45 and rear port RJ-45, each with different rights and default passwords.

Passwords are settable for all predefined user categories. The WHMI password via the front port RJ-45 must be at least four characters and the WHMI password via the rear port RJ-45 at least nine characters. The maximum number of characters is 8 for the WHMI front port password and 20 for the WHMI rear port password. Only the following characters are accepted.

  • Numbers 0-9
  • Letters a-z, A-Z
  • Space
  • Special characters !"#%&'()*+ยด-./:;<=>?@[\]^_`{|}~
Note: User authorization is disabled by default and can be enabled via the LHMI or WHMI path Main Menu > Configuration > Authorization > Passwords.
Table 1. Predefined user categories and default passwords
Username LHMI password WHMI password User rights
VIEWER 0001 remote0001 Only allowed to view
OPERATOR 0002 remote0002 Authorized to make operations
ENGINEER 0003 remote0003 Allowed to change protection relay parameters, but no operation rights
ADMINISTRATOR 0004 remote0004 Full access
Note: For user authorization for PCM600, see PCM600 documentation.