Setting communication between merging units and PCM600 - Arc protection - Bay control and measurement - Merging unit - Operation Manual - SMU615 Substation Merging Unit - 1.0 - IEC - ANSI - 06.06.2023

SMU615 Operation Manual

The communication between the merging unit and PCM600 is independent of the used communication protocol within the substation or to the NCC. It can be seen as a second channel for communication.

The media is always Ethernet and communication is based on TCP/IP.

Each merging unit has an Ethernet front connector for PCM600 access. Depending on the station concept and the used station protocol, additional Ethernet interfaces may be available on the rear side of the merging unit. All Ethernet interfaces can be used to connect PCM600.

When an Ethernet based station protocol is used, the PCM600 communication can use the same Ethernet port and IP address. The merging unit is able to separate the information belonging to the PCM600 dialog.

To configure the physical connection and the IP addresses:

  1. Set up or get the IP addresses of the merging units.
  2. Set up the PC for a direct link or connect the PC or workstation to the network.
  3. Configure the IP addresses in the PCM600 project for each merging unit.
    The addresses are used for communication between merging units and PCM600.