Process bus - Arc protection - Bay control and measurement - Merging unit - Operation Manual - SMU615 Substation Merging Unit - 1.0 - IEC - ANSI - 05.06.2023

SMU615 Operation Manual

Process bus IEC 61850-9-2 defines the transmission of Sampled Measured Values within the substation automation system. International Users Group created a guideline IEC 61850-9-2 LE that defines an application profile of IEC 61850-9-2 to facilitate implementation and enable interoperability. Process bus is used for distributing process data from the primary circuit to all process bus compatible devices in the local network in a real-time manner. The data can then be processed by any protection relay to perform different protection, automation and control functions.

With process bus the galvanic wiring for sharing busbar voltage value can be replaced with Ethernet communication. Transmitting measurement samples over process bus brings also higher error detection because the signal transmission is automatically supervised. Additional contribution to the higher availability is the possibility to use redundant Ethernet network for transmitting SMV signals.

Figure 1. SMU615 sending current measurements as sampled measured values to a protection relay
image/svg+xmlSMVCurrent SensorsProtection and Control RelaySubstation Merging Unit
Figure 2. SMU615 sending voltage measurements as sampled measured values to protection relays
image/svg+xmlSMVProtection and Control RelaySubstation Merging UnitCurrent SensorsVoltageSensor
Figure 3. Smart substation control and protection SSC600 with SMU615
image/svg+xmlSMV and GOOSESmart Substation Control and ProtectionSubstationMerging Unitwith Binary I/0Current Sensors

The merging unit supports IEC 61850 process bus with sampled values of analog currents and voltages. The measured values are transferred as sampled values using the IEC 61850-9-2 LE protocol which uses the same physical Ethernet network as the IEC 61850-8-1 station bus. The intended application for sampled values is sharing the measured voltages and currents from the merging unit to other devices with 9-2 support.

The merging units with process bus based applications use IEEE 1588 v2 Precision Time Protocol (PTP) according to IEEE C37.238-2011 Power Profile for high accuracy time synchronization. With IEEE 1588 v2, the cabling infrastructure requirement is reduced by allowing time synchronization information to be transported over the same Ethernet network as the data communications.

Figure 4. Example network topology with process bus, redundancy and IEEE 1588 v2 time synchronization
image/svg+xmlIEC 61850 HSRSMV trafficBackup 1588master clockManaged HSREthernet switchPrimaryIEEE 1588 v2 master clockSecondaryIEEE 1588 v2 master clock(optional)Managed HSREthernet switch

The process bus is available for all merging units. See the IEC 61850 engineering guide for detailed system requirements and configuration details.