LED indications - Arc protection - Bay control and measurement - Merging unit - Operation Manual - SMU615 Substation Merging Unit - 1.0 - IEC - ANSI - 06.06.2023

SMU615 Operation Manual

Ready LED indicator

Table 1. Ready LED indications
LED state Description
Off Auxiliary supply voltage is disconnected.
On Normal operation.
Flashing Internal fault has occurred or the protection relay is in test mode. Internal faults are accompanied by an indication message.

Alarm indicators

The 11 matrix programmable LEDs are used for alarm indication.

Table 2. Alarm indications
LED state Description
Off Normal operation. All activation signals are off.
On
  • Non-latched mode: activation signal is still on.
  • Latched mode: activation signal is still on, or it is off but has not been acknowledged.
  • Latched flashing mode: activation signal is still on but has been acknowledged.
Flashing
  • Non-latched flashing mode: activation signal is still on.
  • Latched flashing mode: activation signal is still on, or it is off but has not been acknowledged.