Internal faults - Arc protection - Bay control and measurement - Merging unit - Operation Manual - SMU615 Substation Merging Unit - 1.0 - IEC - ANSI - 06.06.2023

SMU615 Operation Manual

An event about the fault is stored as a message on the WHMI. The text Internal Fault with an additional text message, a code, date and time, is stored to indicate the fault type.

Different actions are taken depending on the severity of the fault. The merging unit tries to eliminate the fault by restarting. After the fault is found to be permanent, the merging unit stays in the internal fault mode. All other output contacts are released and locked for the internal fault. The merging unit continues to perform internal tests during the fault situation.

The internal fault code indicates the type of internal fault. When a fault appears, the code must be recorded so that it can be reported to ABB customer service.

Table 1. Internal fault indications and codes

Fault indication

Fault code

Additional information

Internal Fault System error

2

An internal system error has occurred.

Internal Fault File system error

7

A file system error has occurred.

Internal Fault Test

8

Internal fault test activated manually by the user.

Internal Fault

SW watchdog error

10

Watchdog reset has occurred too many times within an hour.

Internal Fault

SO-relay(s),X100

43

Faulty Signal Output relay(s) in card located in slot X100.

Internal Fault

SO-relay(s),X110

44

Faulty Signal Output relay(s) in card located in slot X110.

Internal Fault

PO-relay(s),X100

53

Faulty Power Output relay(s) in card located in slot X100.

Internal Fault

PO-relay(s),X110

54

Faulty Power Output relay(s) in card located in slot X110.

Internal Fault Conf. error,X000

62

Card in slot X000 is wrong type, is missing, does not belong to original configuration or card firmware is faulty.

Internal Fault Conf. error,X100

63

Card in slot X100 is wrong type or does not belong to the original composition.

Internal Fault Conf. error,X110

64

Card in slot X110 is wrong type, is missing or does not belong to the original composition.

Internal Fault Conf. error,X120

65

Card in slot X120 is wrong type, is missing or does not belong to the original composition.

Internal Fault Conf.error,X130

66

Card in slot X130 is wrong type, is missing or does not belong to the original composition.

Internal Fault Card error,X000

72

Card in slot X000 is faulty.

Internal Fault Card error,X100

73

Card in slot X100 is faulty.

Internal Fault Card error,X110

74

Card in slot X110 is faulty.

Internal Fault Card error,X120

75

Card in slot X120 is faulty.

Internal Fault Card error,X130

76

Card in slot X130 is faulty.

Internal Fault LHMI module

79

LHMI module is faulty. The fault indication may not be seen on the LHMI during the fault.

Internal Fault RAM error

80

Error in the RAM memory on the CPU card.

Internal Fault ROM error

81

Error in the ROM memory on the CPU card.

Internal Fault EEPROM error

82

Error in the EEPROM memory on the CPU card.

Internal Fault FPGA error

83

Error in the FPGA on the CPU card.

Internal Fault RTC error

84

Error in the RTC on the CPU card.

Internal Fault COM card error

116

Error in the COM card.