Defining Ethernet port settings - Arc protection - Bay control and measurement - Merging unit - Operation Manual - SMU615 Substation Merging Unit - 1.0 - IEC - ANSI - 06.06.2023

SMU615 Operation Manual

Note: Change the Ethernet port settings primarily via PCM600 to ensure that PCM600 is able to export a consistent configuration to SYS600.

Ethernet port settings are recommended to be changed only when the device is stand-alone and properly configured.

  1. Click Configuration in the left navigation bar and select Communication.
  2. In the Ethernet submenu, define the Rear port settings.
    • IP address
    • Subnet mask
    • Default gateway of the optional rear port Ethernet connector
  3. 3. Click Write to IED.