Checking binary input circuits - Arc protection - Bay control and measurement - Merging unit - Operation Manual - SMU615 Substation Merging Unit - 1.0 - IEC - ANSI - 16.02.2023

SMU615 Operation Manual

  • Preferably, disconnect the binary input connector from the binary input cards.
  • Check all the connected signals so that both the input level and the polarity are in accordance with the protection relay specifications.
CAUTION: Do not use AC voltage. Binary inputs are rated for DC voltage only.