SMU615 Operation Manual

The merging unit offers a large set of event-logging functions. Critical system and merging unit security-related events are logged to a separate nonvolatile audit trail for the administrator.

Audit trail is a chronological record of system activities that allows the reconstruction and examination of the sequence of system and security-related events and changes in the merging unit. Both audit trail events and process related events can be examined and analyzed in a consistent method with the help of Event List in WHMI and Event Viewer in PCM600.

The merging unit stores 2048 audit trail events to the nonvolatile audit trail. Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit trail and event list work according to the FIFO principle. Nonvolatile memory is based on a memory type which does not need battery backup nor regular component change to maintain the memory storage.

Audit trail events related to user authorization (login, logout, violation remote and violation local) are defined according to the selected set of requirements from IEEE 1686. The logging is based on predefined user names or user categories. The user audit trail events are accessible with IEC 61850-8-1, PCM600 and WHMI.

Table 1. Audit trail events
Audit trail event Description

Configuration change

Configuration files changed

Firmware change

Firmware changed

Firmware change fail

Firmware change failed

Attached to retrofit test case

Unit has been attached to retrofit case

Removed from retrofit test case

Removed from retrofit test case

Control remote

DPC object control remote

Test on

Test mode on

Test off

Test mode off

Reset trips

Reset latched trips (TRPPTRC*)

Time change

Time changed directly by the user. Note that this is not used when the merging unit is synchronised properly by the appropriate protocol (IEEE 1588 v2).

View audit log

Administrator accessed audit trail

Login

Successful login from IEC 61850-8-1 (MMS), WHMI or FTP.

Logout

Successful logout from IEC 61850-8-1 (MMS), WHMI or FTP.

Password change

Password changed

Firmware reset

Reset issued by user or tool

Audit overflow

Too many audit events in the time period

Violation remote

Unsuccessful login attempt from IEC 61850-8-1 (MMS), WHMI or FTP.

Violation local

Unsuccessful login attempt from IEC 61850-8-1 (MMS), WHMI or FTP.

PCM600 Event Viewer can be used to view the audit trail events and process related events. Audit trail events are visible through dedicated Security events view. Since only the administrator has the right to read audit trail, authorization must be used in PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data. Audit trail events can be configured to be visible also in WHMI Event list together with process related events.

Note: To expose the audit trail events through Event list, define the Authority logging level parameter via Configuration > Authorization > Security. This exposes audit trail events to all users.
Table 2. Comparison of authority logging levels
Audit trail event Authority logging level

None

Configuration change

Settings edit

All

Configuration change

●

●

●

Firmware change

●

●

●

Firmware change fail

●

●

●

Attached to retrofit test case

●

●

●

Removed from retrofit test case

●

●

●

Control remote

●

●

Test on

●

●

Test off

●

●

Reset trips

●

●

Time change

●

View audit log

●

Login

●

Logout

●

Password change

●

Firmware reset

●

Violation local

●

Violation remote

●