System status registers - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX640 Protection and control - PCL4 - IEC - ANSI - 16.02.2023

REX640 Modbus Communication Protocol Manual

The Modbus SSRx 16-bit system status registers are by default located at addresses 40128...40133. See the Modbus memory map for the actual locations of the SSRx registers. The SSRx registers can also be read from the 3X register area from corresponding register addresses.

Table 1. System status registers
Register Description Address
SSR1 Device health

40128

SSR2 Device mode

40129

SSR3 Data available 1

40130

SSR4 Data available 2

40131

SSR5 Device alive counter

40132

SSR6 Last command result

40133