Single event record structure - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX640 Protection and control - PCL4 - IEC - ANSI - 16.02.2023

REX640 Modbus Communication Protocol Manual

The Modbus event record structure is located at addresses 49251...49262.

Table 1. Event record structure
Address Register Values Comment
49251 Event selection

1...5 and -1...-499

Write register
49252 Sequence Number 0...65535
49253 Unread records left 0...499
49254 TimeStamp (Year,Month) High byte:year, low byte:month
49255 TimeStamp (Day, Hour) High byte:day, low byte:hour
49256 TimeStamp (Min, Sec) High byte:min, low byte:second
49257 TimeStamp (Milliseconds) Word: milliseconds (0...999)
49258 Event type See separate description
49259 Data Object ID 1 0 or UID high word See separate description
49260 Data Object ID 2 Modbus address or UID low word
49261 Data Value Modbus data value Value into which object has changed
49262 Data Value Additional data

The event record can have two different data object identification alternatives. The data object can be identified by the Modbus address where the object resides or it can be identified by a unique id which is platform dependent.

The identification alternative is selected with the Modbus parameter Event ID.