SSR3 - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX640 Protection and control - PCL4 - IEC - ANSI - 16.02.2023

REX640 Modbus Communication Protocol Manual

The data available 1 SSR3 register is located by default at address 40130. The bit values in the SSR3 register are Modbus client dependent.

Bits 0 and 1 are set to "1" as long as the client in question has not read out the available Modbus event or fault records.

Bit 4 is set to "1" if any momentary bit has been updated in the Modbus memory map. The bit is reset when the client reads the register.

Bit 5 is set to "1" if any MCD bit has been set in the Modbus memory map. The bit is reset when the client reads the register.

Bit 6 is set to "1" to indicate the device restart. The bit is reset when the client reads this register.

Bit 8 is set to "1" when an event record has been loaded into registers 49252...49262. The bit is reset when the client writes the reset code 4 to the event record selection register 49251.

Bit 9 is set to "1" when a fault record has been loaded into registers starting from 49402. The bit is reset when the client writes the reset code 4 to the fault record selection register 49401.

Table 1. 16 bit SSR3 register
Bit Description
0 Unread event records available
1 Unread fault records available
2 0 = not used
3 0 = not used
4 Any MOM bit updated
5 Any indication MCD bit set
6 Device restart bit
7 0 = not used
8 Event record ready for reading
9 Fault record ready for reading
10...15 0 = not used