SSR2 - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX640 Protection and control - PCL4 - IEC - ANSI - 16.02.2023

REX640 Modbus Communication Protocol Manual

The device mode SSR2 register is located by default at address 40129. The bit values in SSR2 are common for all Modbus clients. The bits give an overview of the protection relay's mode. For example, bit 6 is activated if the protection relay's configured time synchronization source is lost.

Table 1. 16 bit SSR2 register
Bit Description
0 Test mode (1= Device is set into test mode)
1...2

Local/Remote states (bit 1= LSB)

00 = Remote – Modbus controls allowed

01 = Station – Modbus controls allowed

10 = Local – Modbus controls not allowed

11 = Off – Modbus controls not allowed

3...5

Active setting parameter setting group (bit 3 = LSB)

001 = Setting group 1

010 = Setting group 2

011 = Setting group 3

100 = Setting group 4

101 = Setting group 5

110 = Setting group 6

6 Protection relay time synchronization failure (1 = Failure)
7 0 = not used
8 Last reset cause (1= Power reset)
9 Last reset cause (1= Watchdog reset)
10 Last reset cause (1= Warm reset)
11...15 0 = not used