Reset time structure - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX640 Protection and control - PCL4 - IEC - ANSI - 16.02.2023

REX640 Modbus Communication Protocol Manual

The time and cause of the protection relay's last reset are stored into this structure. The reset time is taken directly from the protection relay's RTC at the startup. The clock might not be accurate and the data can be corrupted.

Table 1. Reset time structure
Address Register Values Comment
49221 TimeStamp (Year,Month) High byte:year, low byte:month
49222 TimeStamp (Day,Hour) High byte:day, low byte:hour
49223 TimeStamp (Min,Sec) High byte:min, low byte:seconds
49224 TimeStamp (Milliseconds) Word: milliseconds
49225 Time Quality See Time quality table
49226 Cause of reset 1 = Power reset
2 = Watchdog reset
3 = Warm reset
Table 2. Time quality
Bit Meaning Values
15 Time format 0 = Local time
1 = UTC time
14 Time source 0 = Internal (RTC)
13 RTC not synchronized 0 = RTC synchronized
1 = Not synchronized
12 RTC Failure 0 = RTC OK
1 = RTC failure
11...0 Not used 0