Real-time clock structure - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX640 Protection and control - PCL4 - IEC - ANSI - 16.02.2023

REX640 Modbus Communication Protocol Manual

Table 1. Modbus real-time clock structure
Modbus address Register contents Values
Local Time UTC Time
49201 49211 Control register 0...2
49202 49212 Year

2000...9999

49203 49213 Month 1...12
49204 49214 Day 1...31
49205 49215 Hour 0...23
49206 49216 Minutes 0...59
49207 49217 Seconds 0...59
49208 49218 Milliseconds 0...999