Multiple digital inputs mapping - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX640 Protection and control - PCL4 - IEC - ANSI - 16.02.2023

REX640 Modbus Communication Protocol Manual

Digital inputs related to two-bit DPC or DPS objects, for instance circuit breaker and disconnectors, have a multiple mapping in the Modbus address space. The objects’ open and close bits are coded as MOM+MCD bit pair entities. The MCD bit reveals if the object has changed its position several times since the Modbus client last scanned it. The open and close bits are also coded using MOM values only, together with a fault bit. The fault bit is set to "1" when the object is in intermediate (00) or faulty (11) position.

Table 1. Bit treatment
Bits Treatment
Close MOM One 2 bit entity
Close MCD
Open MOM One 2 bit entity
Open MCD
:
Close MOM One 1 bit entity
Open MOM One 1 bit entity
Faulty position MOM One 1 bit entity
:

The MOM values are identical in each entity. The MCD bit is only reset if the MOM bit in the same entity is read.