MODBUS Settings - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Modbus Communication Manual - REX640 Protection and control - Relion Protection and Control - PCL4 - IEC - ANSI - 06.07.2021

REX640 Modbus Communication Protocol Manual

Table 1. Non group settings
Parameter Values (Range) Unit Step Default Description
Operation

1=on

5=off

5=off Enable or disable this protocol instance
Port

1=COM 1

2=COM 2

3=Ethernet - TCP 1

3=Ethernet - TCP 1 Port selection for this protocol instance. Select between serial and Ethernet based communication.
Mapping selection 1...2 1 1 Chooses which mapping scheme will be used for this protocol instance.
Address 1...254 1 1 Unit address
Link mode

1=RTU

2=ASCII

1=RTU Selects between ASCII and RTU mode. For TCP, this should always be RTU.
TCP port 1...65535 1 502 Defines the listening port for the Modbus TCP server. Default = 502.
Parity

0=none

1=odd

2=even

2=even Parity for the serial connection.
Start delay 0...20 1 4 Start delay in character times for serial connection
End delay 0...20 1 4 End delay in character times for serial connections
CRC order

0=Hi-Lo

1=Lo-Hi

0=Hi-Lo Selects between normal or swapped byte order for checksum for serial connection. Default: Hi-Lo.
Client IP 0.0.0.0 Sets the IP address of the client. If set to zero, connection from any client is accepted.
Write authority

0=Read only

1=Disable 0x write

2=Full access

2=Full access Selects the control authority scheme
Time format

0=UTC

1=Local

1=Local Selects between UTC and local time for events and timestamps.
Event ID selection

0=Address

1=UID

0=Address Selects whether the events are reported using the MB address or the UID number.
Event buffering

0=Keep oldest

1=Keep newest

0=Keep oldest Selects whether the oldest or newest events are kept in the case of event buffer overflow.
Event backoff 1...500 1 200 Defines how many events have to be read after event buffer overflow to allow new events to be buffered. Applicable in "Keep oldest" mode only.
ControlStructPWd 1 **** Password for control operations using Control Struct mechanism, which is available on 4x memory area.
ControlStructPWd 2 **** Password for control operations using Control Struct mechanism, which is available on 4x memory area.
ControlStructPWd 3 **** Password for control operations using Control Struct mechanism, which is available on 4x memory area.
ControlStructPWd 4 **** Password for control operations using Control Struct mechanism, which is available on 4x memory area.
ControlStructPWd 5 **** Password for control operations using Control Struct mechanism, which is available on 4x memory area.
ControlStructPWd 6 **** Password for control operations using Control Struct mechanism, which is available on 4x memory area.
ControlStructPWd 7 **** Password for control operations using Control Struct mechanism, which is available on 4x memory area.
ControlStructPWd 8 **** Password for control operations using Control Struct mechanism, which is available on 4x memory area.
Prtl Customization 0...2147483647 1 0 Customization parameter. Please, refer to the protocol manual.