Wall mounting the narrow size relay - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Installation Manual - REX640 Protection and control - Relion Protection and Control - PCL4 - IEC - ANSI - 16.10.2024
REX640 Installation Manual
-
Drill four M5 screw holes according to the dimensional drawing.
Figure 1. Drilling screw holes
- A
- 230.4 ±0.4 mm (9.0709 ±0.01575 in)
- B
- 237 ±0.4 mm (9.3307 ±0.01575 in)
- 1
- M5 hole
-
Mount the M5 screws in the upper holes, but do not tighten them. Leave them 3...4 mm (0.1181...0.1575 in) open.
Figure 2. Mounting M5 screws in the upper holes
- 1
- M5 screws
-
Attach the mounting bracket to the protection relay with M6 screws and tighten the screws to 9 Nm ±5% (6.6381 ft-lb ±5%).
Figure 3. Mounting M6 screws
- 1
- Mounting bracket
- 2
- M6 screws
-
Lift the protection relay to its place on the existing screws on the wall mounting section.
-
Mount the M5 screws in the bottom holes.
-
Tighten all the M5 screws.
Figure 4. Mounting and tightening the M5 screws