Tilt/inclined mounting local HMI - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Installation Manual - REX640 Protection and control - Relion Protection and Control - PCL4 - IEC - ANSI - 16.02.2023
REX640 Installation Manual
-
Make a cutout for the LHMI and drill holes for the raising frame according to the dimensional drawing.
Figure 1. Making a cutout and drilling holes
- A
- 197 ±1 mm (7.7559 ±0.03937 in)
- B
- Ø 6.0 mm (0.2362 in)
- C
- 209 ±1 mm (8.2283 ±0.03937 in)
- D
- 179 ±0.4 mm (7.0472 ±0.01575 in)
- E
- 213 ±0.4 mm (8.3858 ±0.01575 in)
-
Mount the tilt frame to the panel with M5 screws.
Figure 2. Mounting the raising frame
- 1
- Tilt frame
- 2
- M5 screws
-
Tighten the screws to 4 Nm ±5% (2.9502 ft-lb ±5%).
-
Mount the LHMI with the installation brackets.
Figure 3. Mounting the local HMI
- 1
- Installation brackets
Figure 4. Tilt mounted local HMI
- A
- 230.0 mm (9.0551 in)
- B
- 25°
- C
- 236.0 mm (9.2913 in)
- D
- 3.5 mm (0.1378 in)
- E
- 108.0 mm (4.2520 in)