Rack mounting the narrow size relay - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Installation Manual - REX640 Protection and control - Relion Protection and Control - PCL4 - IEC - ANSI - 16.10.2024

REX640 Installation Manual

  1. Attach the protection relay to a 7U rack plate with M6 screws.
  2. Tighten the M6 screws to 9 Nm ±5% (6.6381 ft-lb ±5%).
    Figure 1. Mounting the narrow size protection relay to the rack plate
    image/svg+xml12
    1
    7U rack plate
    2
    M6 screws
  3. Mount the protection relay and rack plate to a 19" rack.

    The rack plate can also be mounted to the rack before the protection relay is attached to it.

  4. Tighten the screws.
Figure 2. Rack mounted narrow size protection relay
image/svg+xml