Rack mounting of two narrow size protection relays with local HMI - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Installation Manual - REX640 Protection and control - Relion Protection and Control - PCL4 - IEC - ANSI - 16.10.2024
REX640 Installation Manual
-
Mount two local HMIs to the rack plate.
-
Mount LHMIs with their own installation brackets to the LHMI cutouts.
-
Install the RJ-45 couplers with a cable to the panel cutouts and connect the cables to the LHMI service port X1.2.
Figure 1. Mounting two local HMIs
- 1
- 7U rack plate
- 2
- LHMI installation brackets
- 3
- RJ-45 couplers with cables
-
Mount the mounting bracket to the relays.
-
Mount the mounting bracket to protection relays with M6 screws.
-
Tighten the M6 screws to 9 Nm ±5% (6.6381 ft-lb ±5%).
Figure 2. Mounting the mounting bracket
- 1
- Mounting bracket
- 2
- M6 screws
-
Attach the rack plate to the mounting bracket with M5 screws.
Figure 3. Mounting M5 screws