Mounting grounding bar kit - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Installation Manual - REX640 Protection and control - Relion Protection and Control - PCL4 - IEC - ANSI - 16.02.2023
REX640 Installation Manual
-
Detach the module from the protection relay.
-
Place the grounding bar between the front plates' bendings and mount it to the front plate with M3 screws and washers.
Figure 1. Mounting grounding bar
- 1
- Module
- 2
- Grounding bar
- 3
- M3 screws and washers
- 4
- Edge with chamfer towards the module's collar screw
-
Tighten the M3 screws to 0.8 Nm ±5% (0.5900 ft-lb ±5%).
-
Install the module back to the same slot in the protection relay.
Figure 2. Installing the module