Tip: Only one LHMI module can be connected to a protection relay.
-
Connect the LHMI’s power connector.
- Check the permitted auxiliary voltage range from the sticker found at the rear side of the LHMI.
- Connect the auxiliary voltage leads to the outermost terminals of the LHMI's power connector plug. The polarity is marked on the LHMI's rear plate close to connector X3.
- Push the power connector plug to the bottom.
- Turn the locking latches to lock position to secure the connector.
-
Connect the LHMI to the protection relay.
- Use a CAT6 S/FTP cable to connect the LHMI to the protection relay. See Accessories and ordering data for the cable options.
- Connect the cable to the X1.1/Main unit connector on the LHMI and to the X0/HMI connector on the protection relay's communication module.
- 1
- USB port
- 2
- RJ-45 ports