Connecting current and voltage inputs - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - Installation Manual - REX640 Protection and control - Relion Protection and Control - PCL4 - IEC - ANSI - 16.02.2023

REX640 Installation Manual

Conventional instrument transformers

Each terminal for CTs/VTs is dimensioned for one 0.5...6.0 mm2 (AWG 20-10) wire or for two wires of maximum 2.5 mm2 (AWG 14).

  • Connect the wires from the CTs/VTs to the correct device according to the phase order and the connection diagram.

Sensors (non-conventional instrument transformers)

Current measurement is based on Rogowski coil and voltage measurement is based on voltage divider. Both current and voltage measurements interface the relay via one RJ45 connector per phase. There are two different sensor input modules available, supporting different IEC standards and having different RJ45 connector pin lay-out.

  • SIM1901 supporting IEC 60044
  • SIM1902 supporting IEC 61869

There are a number of sensor interface adapters available which can be used to connect the sensors to the relay, supporting different scenarios both in green field and retrofit cases. More information can be found in Sensor accessories.

Figure 1. AIM1001 module
image/svg+xml57-240VNVT157-240VNVT257-240VNVT357-240VNVT457-240VNVT51/5ANCT1NCT2NCT3NCT4NCT5 (for residual X1X212345678910123456789101/5A1/5A1/5A0.2/1AS1S2P2P1S1P1P2S2PositiveLoad flowDirectionAIM1001nadadnAnL1L2L3L1L2L3current only)
Figure 2. AIM1001 module (two phase-to-phase VTs)
image/svg+xml57-240VNVT1 (Vab)57-240VNVT2 (Vbc)57-240VNVT3 (Vca)57-240VNVT457-240VNVT51/5ANCT1NCT2NCT3NCT4NCT5 (for residual X1X212345678910123456789101/5A1/5A1/5A0.2/1AS1S2P2P1S1P1P2S2PositiveLoad flowDirectionAIM1001L1L2L3current only)caABC
Figure 3. AIM1002 module
image/svg+xml57-240VNVT157-240VNVT257-240VNVT357-240VNVT4CT11/5ANCT2NCT3NCT4NCT5NCT6 X1X212345678910123456789101/5A1/5A1/5A1/5AS1S2P2P1S1P1P2S2PositiveLoad flowDirectionAIM1002nadadnAnL1L2L3L1L2L31/5AN
Figure 4. AIM1002 module (two phase-to-phase VTs)
image/svg+xml57-240VNVT1 (Vab)57-240VNVT2 (Vbc)57-240VNVT3 (Vca)57-240VNVT4CT11/5ANCT2NCT3NCT4NCT5NCT6 X1X212345678910123456789101/5A1/5A1/5A1/5AS1S2P2P1S1P1P2S2PositiveLoad flowDirectionAIM1002L1L2L31/5ANcaABC
Figure 5. SIM1901 module (VT primary connection phase-to-earth)
image/svg+xmlNVTNCT X41257-2400.2/1AS1P1P2S2PositiveCurrentDirectionL1L2L3SIM1901X14578DFFSensor ISensor UDFFX24578DFFDFFX34578DFFDFF34Sensor ISensor USensor ISensor Us1s2s1s2s1s2(for residual current only)
Figure 6. SIM1901 module (VT primary connection phase-to-phase)
image/svg+xmlNVTNCT X41257-2400.2/1AS1P1P2S2PositiveCurrentDirectionL1L2L3SIM1901X14578DFFSensor ISensor UDFFX2DFFDFFX3DFFDFF34Sensor ISensor USensor ISensor Us1s2s1s2s1s2(for residual current only)45784578
Figure 7. SIM1902 module (VT primary connection phase-to-earth)
image/svg+xmlNVTNCT X41257-2400.2/1AS1P1P2S2PositiveCurrentDirectionL1L2L3SIM1902X11278DFFSensor ISensor UDFFX21278DFFDFFX31278DFFDFF34Sensor ISensor USensor ISensor Us1s2s1s2s1s2(for residual current only)
Figure 8. SIM1902 module (VT primary connection phase-to-phase)
image/svg+xmlNVTNCT X41257-2400.2/1AS1P1P2S2PositiveCurrentDirectionL1L2L3SIM1902X11278DFFSensor ISensor UDFFX2DFFDFFX3DFFDFF34Sensor ISensor USensor ISensor Us1s2s1s2s1s2(for residual current only)12781278