Avoid installation in dusty, damp places.
Avoid places susceptible to rapid temperature variations, powerful vibrations and shocks, surge voltages of high amplitude and fast rise time, strong induced magnetic fields or similar extreme conditions.
-
Check that sufficient space is available.
Sufficient space is needed at the front and rear of the protection relay to allow access to wires and optical fibers to provide sufficient ventilation to the protection relay and to enable maintenance and future modifications.
-
Ensure that flush-mounted protection relays can be added and replaced without excessive dismantling.
CAUTION: If the UL enclosure rating should be higher than Type 1, the HMI unit must be installed behind an observation window. Only the HMI flush-mounting option is supported.
UL listed observation windows:
- FTTA/7, Model AMHMI120CCHTP, manufactured by Allied Moulded Products Inc, measuring overall 302.91 mm × 257.70 mm × 57.68 mm (11.9256 in × 10.1457 in × 2.2709 in), rated for 1, 2, 3, 3R, 4, 4X, 12 and 13.
- Alternatively, any FTTA/7 or NITW rated for 1, 2, 3, 3R, 4, 4X, 12 and 13.