ABB product's settings are divided into setting group (SG) and non-group settings (SP) as needed.
If the division differs in the engineered case, it is possible to map SG and SP settings. In this case, the device functionality is not altered and group 1 is only visible through MMS.
|
Access |
FPN data |
ABB data |
Description |
|---|---|---|---|
|
R |
SG |
SP |
Returning same SP value for all SG groups |
|
W |
SG |
SP |
It is only allowed to write group 1. Writing other groups results in error. |
|
R/W |
SP |
SG |
The value is always redirected to group 1. Other SG group values are set via Parameter Setting in PCM600 or the LHMI menu. |
However, it is possible to edit the group settings from PCM600 and the LHMI menu.