SMV additional settings and backward compatibility - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - Relion Protection and Control - PCL6 - IEC - ANSI - 14.05.2025

REX640 IEC 61850 Engineering Guide

The SMV SmpSynch field is defined to operate in different way in IEC 61850-9-2 Ed 1 and Ed 2.1 standard versions. By default the behavior of this field follows the IEC 61850 edition that is selected in PCM600 tool.

To override the SmpSynch behavior, for backward compatibility reasons, parameter "Smv SmpSynch" format can be used. In Ed 1 mode the SmpSynch values are FALSE/TRUE and in Ed 2.1 mode SmpSynch values are: 0=none, 1=local, 2=global. The relay SMV receiver decoder can accept both however properly. However backwards compatibility might be needed for example for older 3rd party devices.