SCL configuration checklist for ReportControl - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - Relion Protection and Control - PCL6 - IEC - ANSI - 14.02.2023

REX640 IEC 61850 Engineering Guide

REX640 supports 27 data sets out of which six can be defined for GOOSE. Forreporting, the total number of ReportControl blocks is 105 (//Services&/ConfReportControl/@max), which typically means that 21 report data sets canhave five clients (//ReportControl/RptEnabled/@max). It may be easiest to replacethe Services section by the section in the REX640 type data files.

Table 1. Possible errors if imported FPN SCD file contains invalid ReportControl blocks

Condition

Cause

Remedy

The customer IED contains one or more report control blocks having [xx] instantiated clients. The internal IED allows 5 instantiated report clients per report control block at maximum.

Some of the report controls have too many clients.

Check the report control blocks using IEC 61850 Configuration.

Too many reporting clients

Enabled clients are out of valid range for some of the report control blocks.

Using IEC 61850 Configuration, check the enabled clients from Object Properties for all the ReportControl blocks. This must be in the range of 2...5.