SCL configuration checklist for GOOSE - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - Relion Protection and Control - PCL6 - IEC - ANSI - 14.02.2023

REX640 IEC 61850 Engineering Guide

REX640 supports six GOOSE send data sets so //SCL/IED/Services/GOOSE/ @max should not exceed 6. It may be easiest to replace the Services section by the section in the REX640 type data files.

In receiving REX640 device uses APPID in packet detection. It is a standard way, however in some template projects, APPID is not set for send GOOSE. Variable //SCL/Communication/SubNetwork/ConnectedAP/GSE/Address/P/@type for APPID must be defined for each GSE element.

Table 1. Possible errors if imported FPN SCD file contains invalid GOOSE control blocks

Condition

Cause

Remedy

The customer IED contains [xx] GOOSE control blocks. The internal IED allows 6 GOOSE control blocks at maximum

There are too many GOOSE control blocks in the imported configuration.

Check the GOOSE control blocks using IEC 61850 Configuration.