REX640 supports six GOOSE send data sets so //SCL/IED/Services/GOOSE/ @max should not exceed 6. It may be easiest to replace the Services section by the section in the REX640 type data files.
In receiving REX640 device uses APPID in packet detection. It is a standard way, however in some template projects, APPID is not set for send GOOSE. Variable //SCL/Communication/SubNetwork/ConnectedAP/GSE/Address/P/@type for APPID must be defined for each GSE element.
|
Condition |
Cause |
Remedy |
|---|---|---|
|
The customer IED contains [xx] GOOSE control blocks. The internal IED allows 6 GOOSE control blocks at maximum |
There are too many GOOSE control blocks in the imported configuration. |
Check the GOOSE control blocks using IEC 61850 Configuration. |