Predefined horizontal communication data sets - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - PCL6 - IEC - ANSI

REX640 IEC 61850 Engineering Guide

In horizontal communication the user normally has to engineer IEC 61850-8-1 GOOSE data sets. When IEC 61850-9-2 is used, the connectivity package automatically creates a data set including data as defined in 9-2 LE: four currents and four voltages with quality attributes. If IEC 61869-9 is used for sampled values, then the data set must be manually configured.

It is not allowed to engineer or modify the predefined 9-2 LE data set. Together with the SMV data sets, the connectivity package also creates a default SMV control block. The SVCB configuration needs to be finalized in the tool before connecting the sent 9-2 LE or IEC 61869-9 data to the receiver IEDs.