Power profile parameters - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - PCL6 - IEC - ANSI - 14.02.2023

REX640 IEC 61850 Engineering Guide

The IEDs' IEEE 1588 v2 time synchronization complies with the IEEE C37.238-2011 Power profile.

For best interoperability, third party devices in the same IEEE 1588 v2 time domain network must be set according to Power profile either via the Power profile parameter or by individually setting the parameters according to Power profile.

Table 1. IEEE C37.238-2011 Power Profile key parameters
Parameter Value 5
Delay Mechanism P2P
VLAN priority mandatory (default=4)
Ethertype 0x88f7
Announce period 1 s
Sync period 1 s
Pdelay period 1 s
PTP mode transparent
5 Some devices use the standard notation format 2x[s] of IEEE 1588 v2 intervals. The values in this table are in [s] format.