Import scenarios - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - PCL6 - IEC - ANSI - 14.02.2023

REX640 IEC 61850 Engineering Guide

The IEC 61850 model provides extensive information tagging for substation automation. The IED data model can be browsed through MMS, and the SCL file provides additional tagging description information. It is possible to have flexible tools which understand the modeling details. PCM600 and ABB-defined data models are recommended for engineering.

On the other hand, if the SCADA/client configuration cannot be changed, for example, in retrofitting and for some standardization changes, there is a need to support IED 61850 configuration changes through FPN.

Figure 1. Retrofit workflow for an existing IED
image/svg+xmlSCADAOld IEDOld IED configurationtoolSystemconfigurationtoolREX640PCM600FPNconfigurationIEC 61850-8-1ReplacesCIDSCDSCDSCDMinimal changes

IEC 61850 allows usage of templates in engineering. If customer specification defines system configuration (SCD), it is possible to use it and continue engineering in PCM600.

Figure 2. Customer-specification based workflow
image/svg+xmlSCADAREX640PCM600FPNconfigurationSystemconfigurationtoolCustomerspecificationIEC 61850-8-1IIDSCDSCDMinimal changes