GOOSE simulation - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - PCL6 - IEC - ANSI - 14.02.2023

REX640 IEC 61850 Engineering Guide

When the IEC 61850 Edition 2 configuration has been selected for the protection relay, it is capable of processing simulated messages. The switchover to simulated messages requires that the relay is set to allow simulated messages and that it receives the first simulated message. Detection of simulated messages is separated per GOOSE publisher. Therefore, one GOOSE input may receive a simulated message while another input receives a real GOOSE message.

Figure 1. Receiving of GOOSE data in case of simulation or test mode
image/svg+xmlTarget Data Value and Quality Are Updated AccordinglyDevice In Test Mode?Test Diagnostic Counter +1GOOSE message receivedReceiver Edition >1?FALSETRUESimulation bit set in received frame?FALSETRUEDevice allows simulation?Test=TRUE set in received frame’s PDU?TRUETRUETRUETRUEFALSEFALSEKeep old valueReceived data quality=test?Device in test mode?TRUEReceived data quality=test?Device in test mode?TRUETRUETRUESet default value and mark data invalidFALSEReceivedalready one simulated message?Device allows simulation?TRUEReject frameTRUEFALSEFALSEKeep old valueFALSEFALSEReject frameFALSE

To set the protection relay to allow simulated GOOSE, either LD0.LPHD1.Sim is set to true via the IEC 61850 protocol or the Allow simulation parameter is set via the WHMI or the LHMI to "Yes".

Figure 2. Setting of the Allow simulation parameter via the Testing and Commissioning page
image/svg+xml

Switching back to receiving real GOOSE messages requires that the Allow simulation parameter is set to "No" (or LD0.LPHD1.Sim = false). The values change to real ones after the first received real GOOSE message.

The LHMI can be used to verify that a simulated GOOSE is received. The publisher is marked with the “(simulated)” text when simulated messages are received.

Figure 3. Subscribed GOOSE publishers on the LHMI during the simulation