From the IEC 61850 point of view, functional constraints should match between the ABB model and the FPN model. It is possible to map data between known predefined functional constraints. For example, different devices may have different requirements of setting group handling. When the FPN model is used for monitoring, a warning message can be ignored.
|
FPN model |
ABB model |
Description |
|---|---|---|
|
SP |
SG |
|
|
SG |
SP |
|
|
SV |
ST, MX ,DC |
REX640 does not support substitution. It is, however, possible to have substation data in the FPN data model and map it to the REX640 application data. |
|
BL |
ST |
Not supported by REX640 directly, but it is possible to map to generic data. |
|
OR |
ST |
Not supported by REX640 directly, but it is possible to map to generic data. |
|
SR |
ST, DC |
Not supported by REX640 directly, but it is possible to map to generic data. |