Editing ReportControl blocks in IEC 61850 Configuration - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - Relion Protection and Control - PCL6 - IEC - ANSI - 14.02.2023

REX640 IEC 61850 Engineering Guide

To edit ReportControl blocks, IEC 61850 configuration engineering mode must be enabled from options.

Figure 1. Enabling IEC 61850 Configuration engineering mode
image/svg+xml
  1. To open IEC 61850 Configuration, right-click an IED and select IEC 61850 Configuration.
    Figure 2. Opening IEC 61850 Configuration
    image/svg+xml
  2. On the toolbar, select Client-Server Communication from the drop-downmenu.
    Figure 3. Selecting client-server communication
    image/svg+xml
  3. Click the Data Sets tab to edit data sets for report controls and the Report Controls tab to edit ReportControl blocks.
  4. To edit the clients for each ReportControl block, select a ReportControl block and open Clients from Object Properties.

One ReportControl block can have a maximum of five clients.