Creating data sets with IEC 61850 Configuration - Arc protection - Auto synchronization - Bay control and measurement - Merging unit - Transformer protection - 2 winding - Feeder protection - Voltage regulation - Capacitor bank protection - Petersen Coil control - Grid automation - Busbar differential protection (high impedance) - Back-up protection - Motor protection - Busbar protection (voltage and frequency) - Transformer protection - 3 winding - Interconnection protection - Generator protection - Power management/Load shedding - IEC 61850 Engineering Guide - REX640 Protection and control - PCL6 - IEC - ANSI - 14.02.2023

REX640 IEC 61850 Engineering Guide

  1. Select Plant Structure in the Project Explorer window.
  2. Right-click the IED node.
  3. Select Client-Server Communication in the drop-down box on the toolbar.
    Figure 1. Selecting Client-Server Communication
    image/svg+xml
  4. Select the Data Sets tab.
  5. Right-click the area containing the data set names and select New to add a new data set.
    Figure 2. Creating a new data set
    image/svg+xml
  6. In the Create New Data Set dialog box, define the LN where to place the data set (accept preselected “LD0/LLN0”) and give the data set a unique name.
    Figure 3. Naming the data set
    image/svg+xml
After creating the GOOSE data sets, define the data set entries (data attributes or data objects) for the data sets.